Place of Origin: | China |
---|---|
Brand Name: | SHX |
Certification: | ISO, CE, Soncap,EPA |
Model Number: | SCF-1100 |
Minimum Order Quantity: | 1 set |
Price: | Negotiable |
Packaging Details: | Plyfilm or plywood |
Delivery Time: | 20 working days |
Payment Terms: | L/C, T/T, Western Union, MoneyGram |
Supply Ability: | 50 Sets per Month |
Engine Brand: | Cummins | Alternator Brand: | Farrand, Leroysomer, Stamford |
---|---|---|---|
Cooling System: | Water Cooled | Control Panel: | Deepsea Or Smartgen |
Governor Class: | ISO 8528 | Protection Standard: | IP 23 |
Highlight: | SHX cummins 1000kva generator,KTA38 Engine cummins 1000kva generator,Open Type 1000kva cummins generator |
SHX 1000kva Cummins Diesel Generator Set KTA38 Engine Model Open Type In Stock
Sunkings open type diesel generator stands on heavy duty channel steel baseframe, which is firmly coated with anti-rust paint for long running and well equipped with vibration damping components and accessories. Moreover, the baseframe has hook eyes for convenient moving.
Model No. | STANDBY POWER | PRIME POWER | ENGINE | ALTERNATOR | CONTROLLER | ||
KVA | KW | KVA | KW | ||||
SCS1100 | 1100 | 880 | 1000 | 800 | KTA38-G5 | Stamford | 6110 |
230/400VAC,50Hz,0.8PF (lag),Three phase four wire
Generator set specifications
Governor Class | ISO8528 G3 |
Potential Drop | 土1% |
Steady Voltage Regulation | 土1% |
Frequency Drop | Synchronous(0%) |
Steady-state Frequency | 土0.25% |
R.R.I.Suppression | BS EN 61000-6-4 / BS EN 61000-6-2 |
Fuel Consumption Rate ,g/kw.h(L/hr) | 209L |
Starting Battery Capacity ,A/hrhhr | 200*4 |
Total Coolant Capacity ,L | 124 |
Fuel Capacity (base tank),L | N/A |
Engine Data
Model | KTA38-G5 |
Type | “V” Type 12 Cylinder,4 Cycle |
Displacement ,L | 37.8 |
Compression Ration | 13.9:1 |
Aspiration | Turbo, Water / Air Cooling |
Fuel System | PT type Fuel Pump,EFC Electronic Governor |
Bore*Stroke(mm) | 159*159 |
Rated Speed ,rpm | 1500 |
Governor Type | Electronic |
Starting Voltage | 24V ,Negative ground |
Battery Charging System | 24V 35A |
Lubricant Capacity ,L | 135 |
Coolant Capacity, L | 258 |
Alternator Data
Protection Class | IP23 |
Insulation Class | Class H |
Temperature Rise in Standard | 125 ℃(When Ambient Temp.is 40 ℃) |
Excitation Type | Brushless & Self-excited |
Waveform Distortion | No load<1.5% Non-Distorting balanced linear load<5% |
Telephone Interference(TIF) | <50 |
Telephone Interference(THF) | <2% |
Pictures for reference:
Generator Set Supply Scope:
1. Engine: Brand-new engine.
2. Alternator: Brand new brushless alternator, single bearing, IP23, H insulation class.
3. Base Frame: Heavy duty steel channel base frame.
4. Radiator: With safety guard.
5. Vibration Damper: Vibration damper between Engine/Alternator and base frame.
6. Breaker: 3 poles output manual circuit breaker.
7. Controller: Deepsea / Smartgen, automatic controller with AMF function.
8. Silencer: Heavy duty industrial type silencer with flexible bellow, elbow.
Genetator test:
1. Loading test: Generators are subjected to a comprehensive performance test which included 0%, 25%, 100% and 110% loading to check and verify the generator running.
2. Parts fault test.
3. Fuel tank pressure test.
4. Bolt tightening torque test.
5. Voltage bearing and insulation test.
6. Noise level test.